4 Zone Wall mount Voice Evacuation Controler EC-4120T

Audio Systems / FTD Audio - EN54-16 Voice Alarm System

4 Zone Wall mount Voice Evacuation Controler EC-4120T

Code: EC-4120T

4 Zone Wall mount Voice Evacuation Controler EC-4120T (120W) Features: Digital voice evacuation system all in one amplifier. Specifications meet the standards of BS EN54-32 & EN608409. EN54-16 standards certificate is under taken. Built-in 2*120W 4 zone class-D amplifier. Integration of EVAC controller, paging system, PA system & BGM system together. Built-in two separate players for EVAC and alert voice message by SD card. Built-in 4 zone speaker line low impedance real time supervision. Built-in amplifier auto changeover into standby when fault. Built-in battery charger to charge the battery. With external amplifier input to expansion the power. Capacity of connection 8 units remote microphones. Red button EVAC message push to activate with priority except fireman microphone. 4 zone speaker outputs with separate zone volume control (ATT). 4 zone separate indicator for EVAC, fault, music/paging & select. System indicators of AC, DC, fault and indicators for EVAC, alert & fireman microphone. Zone capacity of 32 zones by cascaded 7 routers. With 4 zone+1(all zone) programmable zone trigger contacts input and output for voice evacuation system. With Fault, EVAC outputs and Reset input for third party system integration. With fireman microphone of highest priority. Priority level: fireman mic, EMC MIC , EVAC and alert message, Line input & BGM. Two RJ45 ports for router, two RJ45 for remote microphone input AC 230V and DC24V battery input. Auto switch into the battery backup when AC fails. 4 Zone Wall mount Voice Evacuation Controler EC-4120T (120W) Specifications: Model EC-4120T Description 4 Zone Voice Evacuation Amplifier Rated Power Output 120W Fireman Microphone 5Mv, 600Ω Line 1 Inputs 385mV, 10kΩ unbalanced MIC2 Inputs 350mV, 10kΩ, RCA, back up EMC microphone Frequency Response 80Hz~20kHz THD <1% at RMS,1KHz S/N Ratio >70dB Speaker Output 100V 4zone speaker outputs REC Output 200mV Control Input & Output 5 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact 4programmable control outputs: 0V closed contact; Voice Message MP3 or WMA format, two separate players of SD card with protection cover, programmable voice message up to 255, Event Record HEX format, Hard Flash memory, events up to 1000 records, 10 years valid Operation Environment Operation Temp: +5℃ ~ +40℃; Store Temp: -20℃ ~ +70℃; Operation Humidity: Power Consumption 150W Power Supply AC230V or 115V & DC24V battery inputs, 50-60HZ AC Fuse 250V/6.3A, slow type and restorable fuse Dimension 420(W)×450(H)×190(D) mm Weight 12.3kg System function Diagram:

Technical specifications

Model
EC-4120T
Description
4 Zone Voice Evacuation Amplifier
Rated Power Output
120W
Fireman Microphone
5Mv, 600Ω
Line 1 Inputs
385mV, 10kΩ unbalanced
MIC2 Inputs
350mV, 10kΩ, RCA, back up EMC microphone
Frequency Response
80Hz~20kHz
THD
<1% at RMS,1KHz
S/N Ratio
>70dB
Speaker Output
100V 4zone speaker outputs
REC Output
200mV
Control Input & Output
5 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact 4programmable control outputs: 0V closed contact;
Voice Message
MP3 or WMA format, two separate players of SD card with protection cover, programmable voice message up to 255,
Event Record
HEX format, Hard Flash memory, events up to 1000 records, 10 years valid
Operation Environment
Operation Temp: +5℃ ~ +40℃; Store Temp: -20℃ ~ +70℃; Operation Humidity: <95%
Power Consumption
150W
Power Supply
AC230V or 115V & DC24V battery inputs, 50-60HZ
AC Fuse
250V/6.3A, slow type and restorable fuse
Dimension
420(W)×450(H)×190(D) mm
Weight
12.3kg

Applications

Digital voice evacuation system all in one amplifier.
Specifications meet the standards of BS EN54-32 & EN608409.
EN54-16 standards certificate is under taken.
Built-in 2*120W 4 zone class-D amplifier.
Integration of EVAC controller, paging system, PA system & BGM system together.
Built-in two separate players for EVAC and alert voice message by SD card.
Built-in 4 zone speaker line low impedance real time supervision.
Built-in amplifier auto changeover into standby when fault.
Built-in battery charger to charge the battery.
With external amplifier input to expansion the power.
Capacity of connection 8 units remote microphones.
Red button EVAC message push to activate with priority except fireman microphone.
4 zone speaker outputs with separate zone volume control (ATT).
4 zone separate indicator for EVAC, fault, music/paging & select.
System indicators of AC, DC, fault and indicators for EVAC, alert & fireman microphone.
Zone capacity of 32 zones by cascaded 7 routers.
With 4 zone+1(all zone) programmable zone trigger contacts input and output for voice evacuation system.
With Fault, EVAC outputs and Reset input for third party system integration.
With fireman microphone of highest priority.
Priority level: fireman mic, EMC MIC , EVAC and alert message, Line input & BGM.
Two RJ45 ports for router, two RJ45 for remote microphone input
AC 230V and DC24V battery input. Auto switch into the battery backup when AC fails.

Our clients

Our partners

WhatsApp