
Audio Systems / FTD Audio - EN54-16 Voice Alarm System
ECX-4120 4 zones 120W Wall Mount type Voice Alarm System
Code: ECX-4120
4 zones 120W Wall Mount type Voice Alarm System ECX-4120 Features 1.Digital voice evacuation system all in one amplifier. 2.Specifications meet the standards of BS EN54-32 & EN608409. 3.EN54-16 standards certificate is under taken. 4.Built-in 120W 4 zone class-D amplifier. 5.Integration of EVAC controller, paging system, PA system & BGM system together. 6.Built-in EVAC/Alert/BGM message by SD card. 7.Built-in 4 zone speaker BUS real time supervision. 8.Built-in amplifier auto changeover into standby when fault. 9.Built-in battery charger to charge the battery. 10.Capacity of connection 8 units remote microphones. 11.Red button EVAC message push to activate with(programmable) priority except fireman microphone. 12.4 zone speaker outputs with separate zone volume control (ATT). 13.4 zone separate indicator for EVAC, fault, music/paging & select. 14.System indicators of AC, DC, fault and indicators for EVAC, alert & fireman microphone. 15.Zone capacity of 32 zones by cascaded 7 routers. 16.With 4 zone+1(all zone) programmable zone trigger contacts input and output for voice evacuation system. 17.With Fault, EVAC outputs and Reset input for third party system integration. 18.With fireman microphone of highest priority. 19.Priority level: fireman mic, EMC MIC, EVAC and alert message, Line input & BGM(FIFO or FILO). 20.RJ45 port with redundancy for router. 21.AC 230V and DC24V battery input. Auto switch into the battery backup when AC fails. Specification Model ECX-4120 Description 4 Zone Voice Evacuation Amplifier Rated Power Output 120W Fireman Microphone 10mv, 600Ω Line 1 Inputs 775mV, 10kΩ unbalanced MIC2 Inputs 10mV, 10kΩ, RCA, back up EMC microphone Frequency Response 80Hz~20kHz THD <1% at RMS,1KHz S/N Ratio >70dB Speaker Output 100V 4zone speaker outputs Control Input & Output 5 programmable control inputs: Max 3.3V (voltage mode) or 0V closed contact 4programmable control outputs: 0V relay closed contact Voice Message MP3 or WMA format, EVAC/ALERT/BGM, programmable voice message up to 64 Operation Environment Operation Temp: +5℃ ~ +40℃; Store Temp: -20℃ ~ +70℃; Operation Humidity: Power Consumption 150W Power Supply AC230V or 115V & DC24V battery inputs, 50-60HZ AC Fuse 250V/6.3A, slow type and restorable fuse Dimension 420(W)×450(H)×190(D) mm Weight 12.3kg Dimension 484(W)×132(H)×449(D) mm Weight 24kg




















